糸状スペーサを巻いた電線で構成した変圧器巻線の流動・伝熱特性に関する実験的研究 : 第1報,折流板方式との比較
スポンサーリンク
概要
- 論文の詳細を見る
In order to provide higher cooling performance for transformer windings which use nonflammable coolant, conductors wound with thread spacers were applied to the windings to enlarge cooling surface area. Since coolant would flow in the narrow spaces around the conductors, it was necessary to clarify the How and cooling characteristics in the thread spacer windings. Using a two-dimensional winding model, the pressure drop in the windings and the temperature rise in the conductors were measured for different heat fluxes and flow rates. The winding model consisted of model conductors in which thermocouples and thin heater pins were soldered and wrapped in insulating papers. The conductors were wound with thread spacers of 0.75 mm diameter. The temperature rises in these thread spacer windings were found to be significantly lower than those in conventional baffle plate windings. The maximum difference in the temperature rises in the windings was also small and overheating of conductors did not occur at low flow rates in the present test. The pressure drops for the thread spacer windings were predicted as being almost equal to those in baffle plate windings for commercial transformers.
- 一般社団法人日本機械学会の論文
- 1993-05-25
著者
関連論文
- パーフルオロカーボン液を冷媒とした中容量変圧器巻線の基礎的冷却特性
- U形フロー方式による不燃変圧器巻線の基礎的冷却特性
- 糸状スペーサを巻いた電線で構成した変圧器巻線内の流動・伝熱特性に関する実験的研究 : 第2報,スペーサ直径の影響および液冷媒とガス冷媒の比較
- 糸状スペーサを巻いた電線で構成した変圧器巻線の流動・伝熱特性に関する実験的研究 : 第1報,折流板方式との比較
- パーフロロカーボン液を冷媒とした自冷式変圧器の自然循環流動特性と巻線冷却特性
- 不燃変圧器巻線の冷却特性 : 第1報, 強制循環式大容量変圧器の巻線冷却