U形フロー方式による不燃変圧器巻線の基礎的冷却特性
スポンサーリンク
概要
- 論文の詳細を見る
A U-bend coolant supply was applied to transformer windings in an attempt to eqaulize the flow rate in the horizontal coil ducts and to cool windings uniformly. The U-bend supply, which distributes coolant uniformly, is used in heat exchangers. Using a two-dimensional coil cooling model with ten coils, the velocity distribution in the coil ducts and the temperature rise distribution of the coils are measured for the U-bend supply and the Z-shaped supply (baffle plate type). Experiment proves that the cooling characteristics of the U-bend supply are superior to those of the Z-shaped supply at a low flow rate. Computational programs were developed for the U-bend supply and the Z-shaped supply to estimate flow and heat transfer characteristics in the windings. The programs accurately predict the velocity distribution in the coil ducts and the temperature rise distribution of the coils.
- 一般社団法人日本機械学会の論文
- 1991-07-25
著者
-
坂元 健
(株)日立製作所機械研究所
-
山崎 晴幸
日立ニュークリアエンジアリング(株)
-
山崎 晴幸
(株)日立製作所機械研究所
-
中武 良二
(株)日立製作所国分工場
-
上野 善人
(株)日立製作所国分工場