For rationalizing equipment insulation level which can subsequently lead to reductions in the cost of substation equipment such as GIS’s and transformers, it is necessary to reexamine insulating test voltages by investigating the method of evaluating lightning surge waveforms in terms of the equivalent standard lightning impulse waveforms. This paper describes the evaluation method for real surges (called non-standard lightning impulse waveform), based on insulation characteristics of gas gaps. The method is applied to typical surges in the lightning surge time region for various UHV and 500kV systems and it is obtained that the equivalent peak values of the standard lightning impulse waveform are possibly reduced by 20 to 30 percents.
- 社団法人 電気学会の論文
- 2004-01-01
著者
関連論文
- 高圧受電設備での接地方式の違いによる雷保護効果の検証
- 配電線支持方式がフラッシオーバに与える影響に関する実験的検討
- 観測に基づく配電線雷事故率計算手法の開発
- 配電線雷観測に基づく耐雷機材の事故抑制効果の検証
- ナノ/マイクロ複合粒子を充填したエポキシ樹脂の熱伝導性および電気絶縁性の予備的検討
- いくつかの生分解性高分子の部分放電劣化
- エポキシ/アルミナナノコンポジットの創製とトリーイング破壊特性
- ギャップ式分電盤SPD施設時のEMTP解析モデルと基本回路における雷サージ伝搬の検討
- 変圧器励磁突入電流遮断時の急峻な過渡回復電圧
- 超電導限流器を用いた直流限流遮断器の開発