気流ダクトの能動騒音制御における整流用金網の使用
スポンサーリンク
概要
- 論文の詳細を見る
At the application of an Active Noise Control (ANC) for a duct with high speed flow whose velocity is around 12.0 m/s (Reynolds number of 1.0×10^5), the following results for the use of the meshes, as the simplest method for rectifying the flow, were given. The effect of ANC depends on the disturbance velocity attenuation factor of the rectifying meshes. The meshes should not be installed closer to the detection sensor than half the diameter of the duct. The meshes are more effective than the use of thicker sound absorbent materials on the sensors, although the numerical aperture of duct cross-section can be decreased both. The noise reduction effect by use of the meshes were around 3 to 4 dB, without ANC under 200 Hz, and 13dB of noise control effect at 500Hz with the ANC system with the meshes (These effects were measured 100 mm from the duct outlet).