大容量4回線送電線路の保安接地による誘導防護に関する研究
スポンサーリンク
概要
- 論文の詳細を見る
In this paper, we have analyzed the protecting workers on the de-energized circuit from induction due to the live circuit and on the required current capacity of grounding conductor, for security grounding in the work site on 4-circuits large capacity power-line. We have found more suitable phase configuration for the protecting workers from induction due to the live circuit. Then we have made clear the important things to remember for the protecting workers, compared with a 1000 kV power-line. The results are as summarized below. 1. For 4-circuits large capacity power-line, the electromagnetic induction current I(m) flowing through a worker and I_0(m) flowing through the grounding conductor, both currents are more than one hundred times as the electrostatic induction currents. 2. Their exists great difference between values of I(m) and I_0(m) due to kinds of phase configuration. More suitable phase configuration is 4-circuits negative-phase-sequence, which minimize the values of I(m) and I_0(m). For this phase-sequence, the maximum values of I(m) and I_0(m) are limited about 1.5 times on 2-circuits power-line. 3. Even 4-circuits negative-phase-sequence, the maximum value of I(m), in the worke site of 1 km from the grounding point is 16.4 mA. And this value is about 3 times on 1000 kV 2-circuits power-line. Accordingly, in order that I(m) does not exceed 1 mA where is the threshold of human perception, it is necessary to provide the grounding all the working pylons. 4. Even 4-circuits negative-phase-sequence, the maximum value of I_0(m) is 82.6 A. And this value is about 2 times on 1000 kV 2-circuits power-line. But considering fault current flowing through the grounding conductor, the requiered size of one is less than a half one on 1000 kV 2-circuits power-line.
- 東海大学の論文
著者
関連論文
- 混合ガス(N_2, SF_6, c-C_4F_8)の正極性コロナ放電シミュレーション
- 大容量4回線送電線路の保安接地による誘導防護に関する研究
- UHV送電線路の作業用接地による短絡防護に関する考察
- フルイド・マッパーによる複合誘電体界面の電界解析
- 高気圧気体中の放電過程に影響を及ぼす空間電荷のふるまい
- Some Considerations of DC Corona from Rings Arranged on a Conductor
- 導体上に配列された金属突起物による直流コロナの考察(II)
- 紫外線照射ポリプロピレンの誘電的性質
- 導体上に配列された金属突起物による直流コロナの考察
- ポリプロピレンの誘電特性とその劣化について
- 懸垂がいしの衝撃閃絡に関する実験的考察〔?〕
- 富士山配電線の雷害対策に関する調査報告
- 発変電所と送電線の接地
- 気象台データに基づく送電線の熱履歴評価
- 大電流通電時のACSR電線内部の温度分布
- 協会誌「工学(工業)教育」の編集を顧みて
- 1994年度の就職をふりかえって : 採用担当者大いに語る
- パッチクランプ測定装置用磁場曝露デバイス
- これからの工学教育を考える : 若手教員大いに語る