Iodine removal tests for BWR containment spray by large scale facility.
スポンサーリンク
概要
- 論文の詳細を見る
Iodine removal tests for a BWR containment spray were carried out with large-scale JAERI Model Containment Test Facility under LOCA simulated conditions. The tests con-sisted of two groups : "gas-phase based" tests mainly to obtain the initial iodine removal rate by the spray and "liquid-phase based" tests to obtain the iodine partition coefficient at equilibrium state. It was shown that the degree of iodine removal was largely influenced by pH-value of spray water. The results were discussed with calculated results by a code MIRA-PB using a dose reduction factor for the airborne iodine.
- 一般社団法人 日本原子力学会の論文
著者
-
TANAKA Mitsugu
Division of Reactor Safety, Tokai Research Establishment, Japan Atomic Energy Research Institute
-
HASHIMOTO Kazuichiro
Division of Reactor Safety, Tokai Research Establishment, Japan Atomic Energy Research Institute
-
NISHIO Gunji
Division of Reactor Safety, Tokai Research Establishment, Japan Atomic Energy Research Institute
-
NARITOMI Mitsuo
Division of Reactor Safety, Tokai Research Establishment, Japan Atomic Energy Research Institute
-
MOTOKI Yasuo
Division of Reactor Safety, Tokai Research Establishment, Japan Atomic Energy Research Institute
-
KITANI Susumu
Division of Reactor Safety, Tokai Research Establishment, Japan Atomic Energy Research Institute
-
KITANI Susumu
Division of Nuclear Fuel Research, Japan Atomic Energy Research Institute
-
NARITOMI Mitsuo
Division of Health Physics and Safety, Japan Atomic Energy Research Institute
-
NISHIO Gunji
Division of Nuclear Fuel Research, Japan Atomic Energy Research Institute
関連論文
- Behavior of sodium oxide aerosol in closed chamber under thermal convection flow.
- Elemental iodine removal by air-saturated water spray under hypothetical LOCA condition in BWR.
- Iodine removal tests for BWR containment spray by large scale facility.
- Calculation of iodine removal by spray in LWRs containment vessels.
- Selective Collection of Trace Amounts of Radioiodine in Radioactive Sodium Aerosol Utilizing Arc-Discharge Technique
- Calibration of Cascade Impactor by Two-Stage Method