蓄熱槽を有する建物の地下部躯体の温度分布性状に関する研究 : 第1報 地下部躯体の長期温度実測結果とFEM解析
スポンサーリンク
概要
- 論文の詳細を見る
The double slab space composed of foundation slab and footing beams is often used as a heat storage tank of airconditioning system. The temperature of the tank water is about 45 degree of centigrade in winter and about 5 in summer. This hot and chilled tank water causes thermal stresses in the reinforced concrete basement structure. In order to study on the thermal behavior of structures due to heat storage tank, a long term temperature measurement (about one and a half year) of a office building in Tokyo was carried out. The temperature was measured for the water, foundation slab, exterior and interior footing beams, slab and exterior wall of machine room, and so on. From the measured data, the mean temperature and temperature gradient of cross section of member were derived. Unsteady static heat conduction of the building and surrounding soil was analized by 2-dimensional finite element method. The analidcal results were good agreement with the measured data.
- 社団法人日本建築学会の論文
- 1995-05-30
著者
関連論文
- 蓄熱槽を有する建物の地下部躯体の温度分布性状に関する研究 : 第3報 寒冷地(札幌)の場合及び長期蓄熱(1〜50年)の影響に対する検討
- 蓄熱槽を有する建物の地下部躯体の温度分布性状に関する研究 : 第2報 断熱材の厚さ及び地盤の熱物性の影響に関する検討
- 蓄熱槽を有する建物の地下部躯体の温度分布性状に関する研究 : 第1報 地下部躯体の長期温度実測結果とFEM解析
- 蓄熱槽の影響を受けるRC地下外壁の温度応力と温度ひび割れに関する検討