Flow and temperature distributions were measured for natural convection in a rectangular enclosure filled with water. To express a scale model of a residential room with a floor heating system, one of the vertical walls of the test space was cooled to keep the surface temperature almost constant and the bottom wall surface was uniformly heated. Experiments were performed at the Rayleigh number 1.9x10^<10> 〜 3.8x10^<10>. PTV(Particle Tracking Velocimetry) method was applied to measure very slow flow fields, and thermocouple device was employed for temperature field measurements. At near wall regions, detailed data were obtained mainly in a center vertical plane under several heating conditions. These data are arranged to validate numerical methods for the prediction of thermal environments in floor heating rooms.
- 一般社団法人日本機械学会の論文
- 2000-10-01
著者
-
IKEGAMI Hiroshi
Osaka University Graduate School of Medicine
-
Katayama Koichi
Osaka Gas Co. Ltd.
-
Ikegami Hiroshi
Osaka Gas Co. Ltd.
-
Ito Seiichi
Osaka Gas Co. Ltd.
-
Onishi Junji
Dept. Intelligent Machine Engineering Osaka Electro-communication Univ.
-
Mizuno Minoru
Dept. Environmental Engineering, Osaka Univ.
-
Otsuka Nobuyoshi
Mitsubishi Electric Corp.
-
Mizuno Minoru
Dept. Environmental Engineering Osaka Univ.
関連論文
- GENETIC ASSOCIATION OF SUMO4 GENE, AS A CANDIDATE GENE FOR IDDM5, WITH SUSCEPTIBILITY TO TYPE 1 DIABETES IN ASIAN POPULATIONS
- C313 NATURAL CONVECTION IN A RECTANGULAR ENCLOSURE WITH A COOLED VERTICAL WALL AND A UNIFORMLY HEATED BOTTOM SURFACE : PART2-VALIDATION OF A CFD PREDICTION WITH k-ε TWO EQUATION MODELS(Natural convection application)
- C311 NATURAL CONVECTION IN A RECTANGULAR ENCLOSURE WITH A COOLED VERTICAL WALL AND A UNIFORMLY HEATED BOTTOM SURFACE : PART 1 MEASUREMENTS OF FLOW AND TEMPERATURE DISTRIBUTIONS(Natural convection application)
- C109 Numerical Study on the Effect of Latent Heat Storage in a Heating System of a Passive Solar Room(Optical measurement/solar energy)