In-Service Aged Composite Insulators at Transmission Line Investigated by the Micro-Computerized Tomography
スポンサーリンク
概要
- 論文の詳細を見る
Composite insulators aged in-service for almost 10 years at the transmission line of 230 kV, in an area where brittle fracture of a composite insulator occurred, were inspected by the micro-computed tomography, µ-CT, and by the scanning electron microscope, SEM. As a result, several cracks with different depths under pollutant scale and confined in silicone housing were detected by the µ-CT. Surface of silicone housing was observed by the SEM. Many randomly oriented cracks from micrometers size were observed. However, larger cracks detected and evaluated by the µ-CT appear essentially perpendicular to the composite rod axis. In order to explain the evolution of those large cracks in composite insulators, a model based on µ-CT and SEM data was proposed.
- The Japan Institute of Metals and Materialsの論文
著者
-
Monteiro Sergio
CHESF — Companhia Hidroelétrica do São Francisco
-
Silva Pietro
UFPE — Federal University of Pernambuco, Department of Mechanical Engineering
-
Shinohara Armando
UFPE — Federal University of Pernambuco, Department of Mechanical Engineering
-
Pacheco Admilson
UFPE — Federal University of Pernambuco, Department of Mechanical Engineering
-
Castro Filho
CHESF — Companhia Hidroelétrica do São Francisco