Measured data from IT switches are utilized in order to control voltage in distribution systems with photovoltaic generation systems. However, length of period from the data measurement to the data acquisition from IT switches affects voltage control ability in the distribution automation system. In this paper, a voltage control method by LRT and SVR with the periodic data from IT switches is proposed, and using the method, the effect of the length of the data acquisition period for voltage control is evaluated through numerical simulations in a distribution system model. Furthermore, the optimal length of the data acquisition period is determined according to PV penetration rate.