Influence of Arc Discharge on Contact Resistance of AgNi Contacts for Electromagnetic Contactors
スポンサーリンク
概要
- 論文の詳細を見る
Experiments were carried out at several voltages to clarify the influence of the voltage on various characteristics, i.e. arc duration, contact resistance, arc energy, and the change in electrode mass. The voltage was varied from DC100V to 160V, the load current was fixed at 5A constant, and the electromagnetic contactor was operated continuously up to 100,000 times. The experiments were carried out under the three operation modes which are classified by the arc discharge. As a result, the relation between the operation mode and contact resistance was clarified. When only a make arc was generated, the contact resistance was smallest. In addition, the contact resistance was not affected by the source voltage.
著者
-
Suzuki Kenji
Fuji Electric Fa Components & Systems Co. Ltd.
-
Watanabe Masaaki
Fuji Electric FA Components & Systems Co., Ltd.
-
YOSHIDA Kiyoshi
NIT
-
Watanabe Masaaki
Fuji Electric FA Components & Systems Co., Ltd.
-
SAWA Koichiro
NIT
関連論文
- Influence of Voltage on Arc Duration and Electrode Mass Change of AgNi Contacts for Electromagnetic Contactors
- Influence of Voltage on Arc Characteristics and Electrode Mass Change of AgNi Contacts for Electromagnetic Contactors
- Electrode Mass Change of AgNi Contacts for Electromagnetic Contactor : Influence of Voltage when only Break Arc is Generated
- Influence of Arc Discharge on Contact Resistance of AgNi Contacts for Electromagnetic Contactors
- Relation between Electrode Mass Change and Arc Energy of AgNi Contacts for Electromagnetic Contactors