LCフィルタとインバータを併用した大容量アクティブフィルタの開発
スポンサーリンク
概要
- 論文の詳細を見る
Usually, to eliminate the harmonics of transmission lines, LC tuned filters are employed to let bypass these harmonic components. But the elimination ability is limited by its damping resistance. Therefore, active filters composed of high frequency PWM converters are desirable. Comparing with the LC tuned filters, the cost would be very high even in high power systems.In this paper, a low cost and high power active filters for a DC transmission system is proposed. It has active filter ability as well as low cost for high power uses. Its main circuit is composed of conventional LC filters in series with square wave voltage inverters. The voltage of the inverter is controlled to cancel the voltage drop of the internal resistance of the LC filter. So the Q factor of the filter can appear infinity. Calculation of the harmonic and the control are done by DSP (TMS 32010). In the experimental system and simulations, two three phase tuned filter 5-th and 7-th are employed. Excellent results under 1% distortion voltage are obtained.
- 社団法人 電気学会の論文
著者
関連論文
- アキシャルギャップ形超高速高効率モータ
- 太陽電池のファジィモデルを用いた最大出力制御
- LCフィルタとインバ-タを併用した大容量アクティブフィルタとTCRの協調運転
- LCフィルタ併用形大容量アクティブフィルタの開発--制御性改善の一手法
- 瞬時電流制御方式低リプル並列2重インバ-タ
- 空間ベクトルを用いたインバ-タのPWM制御法における制御アルゴリズムの検討
- 中性点接地形3相インバ-タのPWM制御法
- 空間ベクトルを用いた3相電圧形インバ-タの新PWM制御法
- フライホイールエネルギー貯蔵技術を用いた無停電電源装置の開発
- LCフィルタとインバータを併用した大容量アクティブフィルタの開発
- 2台のモ-タを使用したバックラッシュレスサ-ボ機構