高圧配電用避雷器の接地抵抗値が直撃雷保護効果に与える影響
スポンサーリンク
概要
- 論文の詳細を見る
The grounding resistance of surge arresters (Arrs) for the lightning protection of power distribution lines is generally maintained below 30Ω in Japan. Therefore, electric power companies have been spending a large amount of money on the construction and maintenance of low grounding resistances. In this paper, the influence of grounding resistance on lightning protection measures is clarified for power distribution lines with both a ground wire (GW) and Arrs by EMTP analysis and experiments. These results showed that even if the grounding resistance of Arrs becomes high, effectiveness of lightning protection is hardly decreased. Moreover, the results indicated that it is more important for constructing a rational lightning protection system to install a lot of lightning devices on power distribution lines than to lower the grounding resistance of Arrs.