分割型3CT方式における励磁突入電流の異常上昇を防止可能にした計測法の開発
スポンサーリンク
概要
- 論文の詳細を見る
This paper describes the measuring and protection method for the abnormal rise of magnetizing inrush current in a divided type 3 CTs system. By divided type 3 CTs system, it is possible to measure the primary phase current and zero phase current at the same time. In this reason, the divided type 3 CTs system is widely used for the measurement of high voltage distribution line by simply clamping the each phase lines with 3CTs. For the accurate measurement of the phase current and zero phase current, the internal residual current in CT should be small as possible. It is reported that the abnormal rise of the residual current is generated in the practical field use and several ten ampere (converted to the primary current value) is observed in some case. The abnormal rise of the residual current is caused by the primary magnetizing inrush current or by the sum of the influence by electromagnetic field of the nearby conductors. The magnetizing inrush current is caused by the magnetic saturation of the core of CT. It is difficult to eliminate the abnormal residual current by using the bigger size of core. In our test, we used the active elements and independent feed back coils around the right and left core of CT. By using the feed back current from these coils it was observed that the magnetic saturation of the core is improved and the magnetizing inrush current can be controlled.
著者
-
岩崎 文雄
ミドリ電子(株)草加研究室
-
伊部 正之
ミドリ電子(株)草加研究室
-
二野瓶 耕一郎
ミドリ電子(株)草加研究室
-
岡村 清一朗
ミドリ電子(株)草加研究室
-
岡村 清一朗
ミドリ電子 草加研究室
-
伊部 正之
ミドリ電子(株)草加研究室
-
岩崎 文雄
ミドリ電子(株)草加研究室
-
二野瓶 耕一郎
ミドリ電子(株)草加研究室
-
岡村 清一朗
ミドリ電子(株)草加研究室
関連論文
- 分割型3CT方式における励磁突入電流の異常上昇を防止可能にした計測法の開発
- 「屋内配線の活線絶縁診断装置の開発」を読んで
- 高感度分割形ZCTの開発と周辺技術
- トラック型ZCTの巻線方法改善による残留電流低減の検討
- CVCF系統の絶縁監視方法