送電線の電圧・電流を用いた脱調検出方法
スポンサーリンク
概要
- 論文の詳細を見る
A new method of detecting loss of synchronism between groups of generators is proposed. Suppose a group of generators swinging coherently losses synchronism against the remaining generators that also swing coherently. The loss of synchronism can be detected by using the relative phase angle α between current and voltage. The current is measured on a transmission line connecting two sub-networks to which these two groups of generators are belonged respectively and the voltage on a bus connected to the transmission line. Also, the magnitude of current flowing through the transmission line and that of voltage are measured and used for detection. When loss of synchronism takes place between two groups, the relative phase angle α exceeds 90 degrees. Also at the instant when α exceeds 90 degrees, following two conditions hold: the magnitude of voltage is near to the minimum value and that of current is near to the maximum value. These characteristics are used for the method. Theoretical background is explained first and the validity of the proposed method is shown by numerical examples using the model network EAST10.
- 社団法人 電気学会の論文
- 2003-06-01
著者
関連論文
- オンライン安定度計算型系統安定化装置のための外部系統モデル化手法の開発と適用
- 電力系統における需給アンバランスを最小化する系統分離線路の選定法
- 実測データを用いた動的等価回路推定法と電源制限による安定化対策
- 送電線の電圧・電流を用いた脱調検出法の電力系統シミュレータによる検証
- 連系線の電圧・電流の位相差を用いた脱調検出法 : 電力系統シミュレータによる検討
- 送電線の電圧・電流を用いた脱調検出方法
- 多数のループを含む電力系統における位相調整器による効率良い潮流制御法に関する検討
- 脱調予測のための状態推移図を用いた電力相差角曲線上の運転点の追跡法
- 実測データを用いた動的等価回路の安定度判定への適用
- 事故除去直後の電流の影響を反映した電力相差角曲線の精度向上