Energy and Cost Performance of a Cooling Plant System with Indirect Seawater Utilization for Air-Conditioning in a Commercial Building
スポンサーリンク
概要
- 論文の詳細を見る
This paper presents energy and cost performance of a cooling plant system with indirect seawater utilization for air-conditioning in a commercial building. The energy and cost performance is verified by direct measurement and a model-based simulation analysis. In the simulation, the indirect seawater utilization system is compared with a cooling tower system, an air source heat pump chiller system and a direct seawater utilization system. The electric energy consumption of the indirect seawater utilization system is almost the same as the other systems except the air source heat pump chiller system, because using lower seawater temperature can make the efficiency of the refrigerating machine higher, but this system also needs electric energy for cooling seawater/freshwater pumps. However, the indirect seawater utilization system can largely reduce demand charge compared with the cooling tower system, and cut down initial and maintenance costs compared with the direct seawater utilization system. Using these results, the effectiveness of the indirect seawater utilization system toward environmental conservation, energy and cost reduction is clarified in this paper.
- 社団法人日本建築学会の論文
- 2003-05-15
著者
-
Watanabe Toshiyuki
Faculty Of Human-environment Studies Kyushu University
-
Akashi Yasunori
Faculty of Human-Environment Studies, Kyushu University
関連論文
- Habitat System to Maximize Throughput for Sustainable Development
- Ionization-Assisted Deposition of Azo-Containing Polyurea for NLO Applications(Special Issue on Recent Progress in Organic Molecular Electronics)
- Red-Light-Emitting Organic Electroluminescent Devices with Bisanil Dye as Emitter
- Energy and Cost Performance of a Cooling Plant System with Indirect Seawater Utilization for Air-Conditioning in a Commercial Building