In-Situ Performance Test and Simulation of an Air Source Heat Pump
スポンサーリンク
概要
- 論文の詳細を見る
In this study, in-situ Performance test of a 20 RT (70 kW) air-to-air heat pump which has a feature of recovering ventilation energy is carried out. Since test conditions such as indoor and outdoor air conditions cannot be controlled to satisfy the standard test conditions, experiments are done with the inlet air conditions as they exist. From the experimental data obtained with the non-standard test conditions, simulation program is developed to estimate the performance of standard test conditions. The map-based compressor model, ε-NTU method with the assumption of refrigerant-side mixed and air-side unmixed and necessary parameters determined from the measurements are used. From the simulation, performance of a large capacity air source heat pump for various conditions and effects of ventilation are calculated. This study provides method of predicting the performance of air source heat pumps in which in-situ performance test is necessary.
- 2000-11-15
著者
-
Youngil Kim
Thermal Flow Control Research Center Korea Institute Of Science And Technology
-
Kim Youngil
Thermal
-
Baik Young
Thermal
-
Young Jin
Thermal Flow Control Research Center Korea Institute Of Science And Technology
-
Young Soo
Thermal Flow Control Research Center, Korea Institute of Science and Technology
-
Young Soo
Thermal Flow Control Research Center Korea Institute Of Science And Technology
-
Chang Young
Thermal Flow Control Research Center, Korea Institute of Science and Technology
関連論文
- In-Situ Performance Test and Simulation of an Air Source Heat Pump
- G208 IN-SITU PERFORMANCE TEST AND SIMULATION OF AN AIR SOURCE HEAT PUMP(Vapor compression refrigeration system)
- H309 MODELING TRANSFER FUNCTION OF AN ELECTRIC AIR HEATER AND COMPARISON OF CONTROL PERFORMANCES ACCORDING TO CONTROL STRATEGIES(Heat transfer control)