Development of a 3-Dimensional Seismic Isolation Floor for Computer Systems
スポンサーリンク
概要
- 論文の詳細を見る
This paper presents a 3-dimensional seismic isolation floor developed to protect computer systems in nuclear power plants from strong earthquakes. The 3-dimensional seismic isolation floor consists of floor panels, a floor frame, horizontal coil springs, isolation-supporting devices and devices for controlling rocking motion. In order to examine the performance of the 3-dimensional isolation floor, vibration tests of an isolation floor model, on which an actual computer system was set up, were carried out using a 3-dimensional shaking table. Test results confirmed that the actual computer system was effectively isolated by the 3-dimensional seismic isolation floor.Moreover, an analytical model was validated against these test results. For the analytical simulation the floor frame was representdd by five lumped masses and the isolation device was modeled as 2-dimensional springs and dampers. Both the calculated acceleration time history and floor response spectrum agree well with test results.
- 一般社団法人日本機械学会の論文
- 1992-12-15
著者
-
Kurihara Masaki
Mechanical Engineering Research Laboratory Hitachi Ltd.
-
Shigeta Masayuki
Mito Works Hitachi Ltd.
-
NIINO Tsuyoshi
Hitachi Works, Hitachi, Ltd.
-
MATSUKI Tsutomu
Omika Works, Hitachi, Ltd.
-
Niino Tsuyoshi
Hitachi Works Hitachi Ltd.
-
Matsuki Tsutomu
Omika Works Hitachi Ltd.
関連論文
- A Study on Response during Large Deformation in a Seismic Isolation Systemof Nuclear Island Buildings
- Development of a 3-Dimensional Seismic Isolation Floor for Computer Systems