CONSIDERATIONS OF A TWO-PHASE FLOW DIFFUSER DURING SELF-FLASHING PHENOMENON OF HOT WATER IN PIPING
スポンサーリンク
概要
- 論文の詳細を見る
Self-flashing two-phase flow caused erosion damage to the piping just downstream from the constricted parts such as valves, orifices, etc. of the hot water piping. The cause and allowable value of erosion, caused at the diffuser behind valve, were experimentally analyzed using a half-cut diffuser in order to make the observation of inner surface easy. As the result, the intensity of the erosion was affected by the two-phase flow pattern and the divergent angle of the diffuser. The erosion was mainly caused by an eddy flow generated at the diffuser. Allowable values of erosion factors, such as averaged velocity, averaged kinetic pressure and cavitation coefficient, depended on the divergent angle of the diffuser.
- 一般社団法人日本機械学会の論文
著者
-
Nakamura Shozo
Mechanical Engineering Research Laboratory Hitachi Ltd.
-
Matsushima Tokunori
Mechanical Engineering Research Laboratory Hitachi Ltd.
-
MIZUSHINA Yasuo
Mechanical Engineering Research Laboratory, Hitachi, Ltd.
-
HORIKAWA Yoriaki
Hitachi Works, Hitachi, Ltd.
-
Mizushina Yasuo
Mechanical Engineering Research Laboratory Hitachi Ltd.
-
Horikawa Yoriaki
Hitachi Works Hitachi Ltd.
関連論文
- Drypatch Characteristics of a Saturated Water Thin Film in a Rectangular Channel using a Flat-Plate-Type Obstacle : Basic Mechanism
- Pressure Oscillation in Transient Two-Phase Flow Due to Thermal Non-Equilibrium During Rapid Opening of Valve
- Feedforward Temperature Control of Heating Surfaces for Boiling Experiment : 1st Report, Basic Study : Series B : Fluid Engineering, Heat Transfer, Combustion, Power, Thermophysical Properties
- CONSIDERATIONS OF A TWO-PHASE FLOW DIFFUSER DURING SELF-FLASHING PHENOMENON OF HOT WATER IN PIPING
- Research Concerning Feedforward Water Level Control Taking Self-evaporation of Hot Water in Piping into Consideration