Characterized Discharge Current Waveforms of Metal Oxide Surge Arresters on 77kV Power Systems
スポンサーリンク
概要
- 論文の詳細を見る
The behaviors of metal oxide surge arresters installed at substation terminal, generally without spark gaps are well-known by the excellent performances of automatic fault clearance and of reliable overvoltage protection of substation apparatus. As the result of four-year research experiences on the 77kV operating power systems including observed substations T and F halfway between the protection terminals, authors have proved the characterized discharge current of those arresters can be divided into three types of waveforms such as instantaneous heavy pulse, low level lingering continuance and medium continued damping oscillation. The negative lightning discharge with subsequent multiple strokes against de-energized power lines may be the distinct and frequent causes of damping current oscillation of surge arresters. Moreover, the negative discharge current on the sound phase has been encountered not a little in the case of related double-line-to-ground fault. In this paper, the combination of those parameters is clearly expressed through several representing figures of arrester current waveforms together with those of corresponding voltage of surge fronts and 60Hz voltage transients if available.
- 社団法人 電気学会の論文
- 2003-11-01
著者
-
Ueda Toshiaki
Research And Development Division Chubu Electric Power
-
MIYACHI Iwao
Department of Electrical Engineering, Aichi Institute of Technology
-
YODA Masayuki
Department of Electrical Engineering, Aichi Institute of Technology
-
KANEHARA Kazuto
Department of Electrical Engineering, Aichi Institute of Technology
-
Miyachi I
Department Of Electrical Engineering Aichi Institute Of Technology
-
Miyachi Iwao
Department Of Electrical Engineering Faculty Of Engineering Nagoya University
-
Yoda M
Department Of Electrical Engineering Aichi Institute Of Technology
-
Yoda Masayuki
Department Of Electrical And Electronic Engineering Aichi Institute Of Technology
-
Kanehara Kazuto
Department Of Electrical Engineering Aichi Institute Of Technology
関連論文
- Surge Voltages Induced in Secondary Circuits of 275kV Full GIS
- Surge Voltages Induced in Secondary Circuits of 275kV Full GIS
- Characterized Discharge Current Waveforms of Metal Oxide Surge Arresters on 77kV Power Systems
- Characterized Discharge Current Waveforms of Metal-Oxide Lightning Arresters on 77kV Power Systems
- Distance-dependent Travelling-Wave Phenomena detected within Lightning Surge Waveforms at Substation
- Coincidence of Waveforms on Fault-Related Lightning Surges at Substation Terminal
- Characteristics of Multiple Anode Spots on a Cryogenic Copper Electrode during Arc Discharge
- Simulation Research of Single-Phase Centralized Inverter for PV modules with Maximum Power Point Tracking
- Crystallization Process and Electrical Conduction of Poly(vinylidene fluoride)
- Molecular Motion and Electrical Conduction in Poly (vinylidene fluoride)
- First Order Transition and Electrical Conduction of Polyethylene