Performance of heat exchangers in appliances such as air-conditioners, showcase coolers and unit coolers can deteriorate under frosting conditions. To address this issue, the mechanism of frost deposition needs to be investigated. To achieve this goal, the frost formations process was observed and properties of frost were measured at air and cooling surface temperatures less than 0 °C using a refrigeration apparatus. Frost crystals formed on the cooling surface had a needle-like structure under the chilled condition, which represents an air temperature of 0 °C and cooling surface temperature of -10°C. On the other hand, frost crystals formed on cooling surface had a block shaped structure under the frozen condition, which represents an air temperature of -15°C and cooling surface temperature of -29°C. This work examined the relationship between density and thermal conductivity of frost, and calculated Nusselt number and Sherwood number.