水蒸気吸着剤の総括熱物質移動係数―第2報:吸着ロータ層における移動係数―:第2報:吸着ロータ層における移動係数
スポンサーリンク
概要
- 論文の詳細を見る
A fundamental investigation was performed to develop a compact and simple desiccant ventilation unit which is one of the main components of a novel energy saving air-conditioning system. Water vapor in the air is adsorbed and/or desorbed to be controlled the humidity of supply air through a unit of an adsorbent rotor. A numerical simulation helps to understand the phenomena of heat and mass transfer in the rotor block. Overall transfer coefficients were estimated by performing both experiment and calculation. It was examined that the transient overall equivalent heat and mass transfer coefficient was not constant. It seems that both film fluid and diffusion resistance govern the coefficients in the block, and the influence of air flow on the time averaged coefficients is estimated by a considering the laminar forced convection from a flat plate. There is little difference of the coefficient between adsorption and desorption process. The correlation and fitting parameters are presented for prediction of the overall heat and mass transfer coefficients. The estimation accuracy was improved.
- 公益社団法人 日本冷凍空調学会の論文
公益社団法人 日本冷凍空調学会 | 論文
- 液滴の過冷却凝固について:-食塩水溶液-
- 水‐油エマルションを用いた氷蓄熱のための容器内撹はん製氷 臨界表面張力の小さな壁面材質の熱抵抗が製氷過程に与える影響について:臨界表面張力の小さな壁面材質の熱抵抗が製氷過程に与える影響について
- 水‐油エマルションを用いた氷蓄熱のための容器内撹はん製氷 エマルションの組成が製氷過程に与える影響について:(エマルションの組成が製氷過程に与える影響について)
- クロスフィンチューブ熱交換器におけるフィンカラー形状が伝熱性能に及ぼす影響
- マイクロガスタービン・固体酸化物形燃料電池複合発電による分散エネルギーシステムの性能解析と最適運用計画