収着剤ロータを用いた複合式湿度調節システム
スポンサーリンク
概要
- 論文の詳細を見る
This paper describes a new hybrid humidity control system that combines a desiccant rotor with a vapor compression refrigerator. This rotor uses a kind of advanced sorbent and desorption at low temperature below 50°C is possible. Therefore the rotor can be recovered by exhaust heat of a condenser. Applying the new hybrid system, we installed an experimental prototype and investigated its performance. As a result, dehumidification can be achieved even if the absolute humidity of the processing air is less than 0.002 kg/kg'. This suggests that water can be taken out from the exhausting air to humidify the returning air in winter. Furthermore, dehumidification efficiency is 4.1kg/kWh, system COP1.8 for the processing air 30°C, 62%RH. That corresponds with the summer weather condition. If it is winter, the dehumidification efficiency is 1.9kg/kWh, system COP0.97 for the processing air 22°C, 50%RH.