ビル用マルチエアコンの期間性能評価に関する研究―第1報:EHPにおける期間エネルギー消費―:第1報:EHP における期間エネルギー消費
スポンサーリンク
概要
- 論文の詳細を見る
The partial load performance tests of multi-type package air-conditioners for buildings powered by electric motors, the rating cooling performance of which was 56 kW, were carried out by using the air-enthalpy method testing apparatus. The coefficient of performance (COP) and annual energy consumption measured by those tests were closely compared with those estimated from the current calculating method (JIS B 8616:2006). It was found that the performance of the air-conditioner changes depending on the outdoor air temperature and the indoor thermal load. The current calculating method could not reproduce the deteriorations of COP that appeared under the low thermal load condition in both the cooling and heating seasons. As a result it seriously underestimated the annual energy consumption; the error amounted to as large as about 20 % of the measured annual electric power consumption. Based on these results, we have proposed new testing conditions for the performance evaluation and a calculation method of the annual energy consumption that can improve the accuracy of the estimation of the annual energy consumption.