ヒートポンプエアコンの除霜時間短縮
スポンサーリンク
概要
- 論文の詳細を見る
Methods to shorten the defrost time have been studied on a heat pump air conditioner. The experiment has been carried out using a 0.75kW heat pump and the energy balance during defrosting has been analyzed. We have found that the following methods are effective to shorten the defrost time; (1) Increase in power inqut to the compressor during defrosting, (2) Utilization of the compressor for thermal energy storage, (3) Reduction of the water left on the outdoor heat exchanger fins. The heat pump with the new defrosting system has been made on an experimental basis. lts defrost time is 1 minute and 55 seconds under the defrost condition of the Japanese Industrial Standard. The defrost time of a conventional heat pump is about 4 or 5 minutes.
- 公益社団法人 日本冷凍空調学会の論文
公益社団法人 日本冷凍空調学会 | 論文
- 液滴の過冷却凝固について:-食塩水溶液-
- 水‐油エマルションを用いた氷蓄熱のための容器内撹はん製氷 臨界表面張力の小さな壁面材質の熱抵抗が製氷過程に与える影響について:臨界表面張力の小さな壁面材質の熱抵抗が製氷過程に与える影響について
- 水‐油エマルションを用いた氷蓄熱のための容器内撹はん製氷 エマルションの組成が製氷過程に与える影響について:(エマルションの組成が製氷過程に与える影響について)
- クロスフィンチューブ熱交換器におけるフィンカラー形状が伝熱性能に及ぼす影響
- マイクロガスタービン・固体酸化物形燃料電池複合発電による分散エネルギーシステムの性能解析と最適運用計画