クロス溝付管による非共沸混合冷媒の伝熱性能向上 第2報 蒸発実験結果
スポンサーリンク
概要
- 論文の詳細を見る
The evaporation of a zeotropic refrigerant (R 407 C) inside horizontal tubes has been investigated experimentally using two types of new cross-grooved tubes and a conventional single-grooved tube. The cross-grooved tubes were formed by varying the helix angle of a second set of grooves whose fin height was the same as that of the first set. The evaporation in the two types of cross-grooved tubes was compared with that in a smooth surface tube. At low mass flows, the improved cross-grooved tube (second helix angle β2 = 0 °) has shown higher evaporative heat transfer coefficients than the single-grooved tube, but at higher mass flows the single-grooved tube has shown higher. The pressure drop of the cross-grooved tube (second helix angle β2 = -30°) is greater than that of the improved cross-grooved tube.
- 公益社団法人 日本冷凍空調学会の論文
公益社団法人 日本冷凍空調学会 | 論文