スプリンクラーの作動特性と閉鎖空間における作動時間
スポンサーリンク
概要
- 論文の詳細を見る
In order to improve the predictability of sprinkler response time for a confined ceiling, thermal properties of fusible sprinkler and environment of sprinklers below a confined ceiling during fire are discussed. A method of estimating the heat loss from a fusible link of the sprinkler fitting and the response of the link to external radiation is proposed. Measurements of temperature, velocity, radiation, and sprinkler response time below a ceiling are made in a 11.1 m × 8.1 m confined enclosure. The measured temperature and velocity are found to be close to previous theory for an unconfined ceiling if a correction for the existence of smoke layer is applied. Finally measured sprinkler response time is compared with calculation based on measured temperature, velocity and radiation history. The result shows the significance of radiation from the fire source in the determination of sprinkler response times.
- 日本火災学会の論文