Development of a DC Feeding Bus Ground Fault Detection System for Railway Substations
スポンサーリンク
概要
- 論文の詳細を見る
High-voltage DC ground relays (64P) are commonly used at DC railway substations to detect DC feeding bus ground faults, which may cause fire or other serious damage. Therefore, 64P relays, which send a command to open all related circuit breakers, are very important devices. However, 64P relays sometimes disrupt railway traffic because they are occasionally activated by irrelevant faults, such as ground faults at external feeding lines or other substations. We are now developing a new method of detecting DC bus ground faults that can eliminate the influence of unrelated faults. This paper gives an outline of the new method and the results of basic investigation.
- 公益社団法人 鉄道総合技術研究所の論文
公益社団法人 鉄道総合技術研究所 | 論文
- Measurement of the Contact Force of the Pantograph by Image Processing Technology
- Simulation of Passenger Behavior on Board a Commuter Train in the Event of a Level Crossing Accident
- Predicting Concrete Deterioration due to Chloride Corrosion of Reinforcing Bars
- Neutral Point Bias Control Method for Large Capacity Inverter.
- Totally Enclosed Permanent Magnet Synchronous Motor for Commuter Trains