Evaluation of ignitability of fire-retardant-treated-plywood by the ISO ignitability test(II). Influence of description and retention of fire-retardants time of treated-plywoods.:Influence of description and retention of fire-retardants time of treated-pl
スポンサーリンク
概要
- 論文の詳細を見る
The ISO 5657 ignitability test method was conducted to analyse the ignition time of fire-retardant-treated-plywood. Mono-ammonium phasphate, ammonium bromide and a commercial product which consists of ammonium polyphosphate were tested for, fire-retardants. Influence of fire-retardant on ignition time was dependent upon irradiance. When the irradiance level against plywoods was 3W/cm<SUP>2</SUP>, the following retentions of each fire-retardant were needed in the minimum to depress the ignition of them: 70kg/m<SUP>3</SUP> of mono-ammonium phosphate, 80kg/m<SUP>3</SUP> of the tested commercial product and 30kg/m<SUP>3</SUP> of ammonium bromide.