Evaluation of Annual Performance of Multi-type Air-conditioners for Buildings
スポンサーリンク
概要
- 論文の詳細を見る
The partial thermal load performance tests of electric-motor driven multi-type air-conditioners for buildings, the rated cooling and heating capacities of which were 56 kW and 63 kW, respectively, were carried out using the air-enthalpy method testing apparatus. Based on the results of those tests, the applicability of JIS B 8616: 2006, which was developed for the estimation of the annual electricity consumption of packaged air-conditioners with rated cooling capacities less than 28 kW, to the multi-type air-conditioners with larger capacities were examined. It was found that JIS B 8616: 2006 generally overestimates COP under a relatively low thermal load operation. As a result, the annual electricity consumption is underestimated by JIS. The prediction error changes depending of the building uses, and it amounted to -17 % in the case of office and -6 % in the detached shop.
著者
-
Nakayama Hiroshi
Research And Development Division Sony Magnetic Products Inc.
-
Hirota Masafumi
Department Of Mechanical Engineering Mie University
-
HIROTA Masafumi
Department of Mechanical Engineering, Mie University
-
WATANABE Choyu
Research and Development Division, Chubu Electric Power Co., Inc.
-
OHASHI Ei-ichiro
Department of Micro/Nano Systems Engineering, Nagoya University
-
NAGAMATSU Katsuaki
Research and Development Division, Chubu Electric Power Co., Inc.
関連論文
- Experimental Study on Turbulent Flow and Mixing in Counter-Flow Type T-Junction
- Turbulent Mixing Measurement in a Counter-Type Mixing Flow
- Flow Characteristics in a Counter-Flow Type T-junction
- Design Concept of Magneto-Optical Disk : MAGNETO-OPTICAL MEDIA III
- Experimental Study on Gas-Liquid Flow Distributions in Upward Multi-pass Channels
- Evaluation of Annual Performance of Multi-type Air-conditioners for Buildings