Coupled-Calculation of Three Dimensional Thermal and Fluid Fields In 27.5 kV GIS Bus Bar's Cabinet
スポンサーリンク
概要
- 論文の詳細を見る
Based on the heat conduction equation, fluid flow governing equation and radiation heat transfer equation, the multi-physics coupled mathematical model is established, the convection heat transfer problem between solid and fluid is solved by wall function, the three dimensional thermal and fluid fields of 27.5kV GIS which is used in the distribution system of high-speed railway are calculated and analyzed by the finite volume method. The result shows that the three-position isolation switch in the GIS is the hottest. The computed temperature rises have good agreement with the tested ones; it can prove that this mathematical model and numerical method are reasonable.
- 2010-11-04
著者
-
Liu Weidong
Department Of Electrical Engineering Tsinghua University
-
Zhang Junmin
School of Automation Science and Electrical Engineering, Beijing University of Aeronautics and Astro
-
Hou Zhenhua
School of Automation Science and Electrical Engineering, Beijing University of Aeronautics and Astro
-
Zhang Chunpeng
Department of Electrical Engineering, Tsinghua University
-
Jiang Qirong
Department of Electrical Engineering, Tsinghua University
-
Hou Zhenhua
School Of Automation Science And Electrical Engineering Beijing University Of Aeronautics And Astron
-
Zhang Chunpeng
Department Of Electrical Engineering Tsinghua University
-
Zhang Junmin
School Of Automation Science And Electrical Engineering Beijing University Of Aeronautics And Astron
-
Jiang Qirong
Department Of Electrical Engineering Tsinghua University
-
Zhang Junmin
School Of Automation Science And Electrical Engineering Beijing University Of Aeronautics And Astron
-
Zhang Chunpeng
Department of Cardiovascular surgery, Akita University Graduate School of Medicine
関連論文
- Coupled-Calculation of Three Dimensional Thermal and Fluid Fields In 27.5 kV GIS Bus Bar's Cabinet
- Calculation of Characteristic Parameters and Research of Fault Diagnosis for Aircraft Wires Existed Insulation Defects
- Coupled-Calculation of Three Dimensional Thermal and Fluid Fields In 27.5kV GIS Bus Bar's Cabinet
- DOWN-REGULATION OF L-TYPE CA2+ CURRENT IN LEFT ATRIAL MYOCYTES OF RATS DURING EXPERIMENTAL CARDIAC HYPERTROPHY