Thermal and Ventilation Characteristics in a Workstation Area by Personal Air-Conditioning System
スポンサーリンク
概要
- 論文の詳細を見る
This paper investigates thermal and ventilation characteristics in a workstation area of an office building equipped with a personal environmental system. An under-floor air-conditioning system with and without a desk-mounted PEM (Personal Environmental Module) is compared. A tracer gas experiment using SF6 gas is performed to measure the local supply index and the room mean ventilation effectiveness. The particle image velocimetry is utilized to obtain quantitative velocity vectors in the workstation area for various supply air conditions. As a result, the local supply index in the workstation area is found to be increasing by operating a PEM, while overall room ventilation effectiveness remains the same. Flow visualization results show upward buoyant flows for a heating condition, and there is a need to adjust the angle of the PEM diffuser grille.
- 社団法人日本建築学会の論文
- 2002-11-20
著者
-
Chung Kwang-seop
Department Of Architectural Engineering Seoul National University Of Technology
-
Yee Jurng-Jae
Faculty of Architectural Design & Engineering, Dong-A University
-
Han Hwataik
School of Mechanical & Automotive Engineering, Kookmin University
-
Park Young-Chil
Department of Control & Instrumentation Engineering, Seoul National University of Technology
-
Yee Jurng-jae
Faculty Of Architectural Design & Engineering Dong-a University
-
Park Young-chil
Department Of Control & Instrumentation Engineering Seoul National University Of Technology
-
Han Hwataik
School Of Mechanical & Automotive Engineering Kookmin University
関連論文
- Transient Temperature Responses of Hydronic Radiant Floor Heating System by Different Pipe Embedding Depth and Water Supply Condition
- Thermal and Ventilation Characteristics in a Workstation Area by Personal Air-Conditioning System