オゾン層保護のための代替フロン採用におけるキャピラリチューブ閉塞
スポンサーリンク
概要
- 論文の詳細を見る
When the refrigerant for refrigerator was switched from CFC12 to HFC134a for the preservation of the ozone layer, the refrigerant oil also had to be changed from mineral oil to ester oil for securing miscibility. Ensuring efficiency and lubricity has surely and steadily advanced but a trouble of capillary tube clogging has occurred. The blockage of a capillary tube is identified to have been caused by the mold lubricant of the plastic components adopted inside the compressor, which led the sludge accumulation mechanism to elucidation. On the basis of this outcome it came to be possible to prevent the blockage of capillary tube perfectly.