Design and Performance of a Transformerless Shunt Hybrid Active Filter for Installation on a 6.6-kV Power Distribution System
スポンサーリンク
概要
- 論文の詳細を見る
This paper presents the analysis and design of a shunt hybrid active filter for harmonic damping in a 6.6-kV power distribution system. This hybrid filter has been proposed and tested experimentally with a 200-V, 20-kW laboratory system, showing good damping performance. Another possible solution for harmonic damping is to install a shunt pure active filter at the end of a feeder. However, the pure filter is too costly and bulky to be installed in a 6.6-kV system. This paper discusses the design criteria for a hybrid filter intended for installation on a 6.6-kV power distribution system. Detailed comparisons between the pure filter and the hybrid filter are also included as a foundation for the design of the hybrid filter. The performed design confirms the feasibility of installation of the hybrid filter on a 6.6-kV power distribution system.
- 社団法人 電気学会の論文
- 2006-04-01
著者
関連論文
- Cooperative Control of Shunt Active Filters for Harmonic Damping throughout Power Distribution Systems : Implementation of Automatic Gain Adjustment
- A Transformerless Shunt Hybrid Filter for Harmonic Filtering of a Three-Phase Diode Rectifier
- Bi-Directional Isolated DC-DC Converter for Next-Generation Power Distribution : Comparison of Converters Using Si and SiC Devices
- Stability Improvement of a Series Active Filter Integrated with a Double-Series Diode Rectifier
- Design and Performance of a Transformerless Shunt Hybrid Active Filter for Installation on a 6.6-kV Power Distribution System