The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model (特集:平成17年〔電気学会〕電力・エネルギー部門大会)
スポンサーリンク
概要
- 論文の詳細を見る
In order to analyze the potential gradient of ground surface of grounding system installed in buildings, the hemispherical grounding simulation system has been designed and fabricated as substantial and economical measures. Ground potential rise (GPR) has been measured and analyzed for shapes of a mesh grid grounding electrode by using the system. The system is apparatus to have a free reduced scale for conductor size and laying depth of a full scale grounding system. When a current flows through a grounding electrode, the system is constructed so that a shape of equipotential surface is nearly identified a free reduced scale model with a real scale model.The system was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The water tank was made of stainless steel and its diameter was 2m. AC power supply produced earth leakage current. GPR was measured by a moving probe of a potentiometer horizontally. The test grounding electrodes were fabricated through reducing grounding electrode installed in real buildings such as a mesh grid type, a combined type and so on. GPR has been measured in real time when a test current has flowed through grounding electrode. GPR was displayed in two-dimensional profile and was analyzed for shapes of a grounding electrode. When a mesh grid type was associated with a rod type and auxiliary mesh electrodes were installed at the four sides of mesh grid grounding electrode, GPR was the lowest of all test grounding electrodes. The proposed results would be applicable to evaluate GPR in the grounding systems, and the analytical data can be used to stabilize the electrical installations and prevent the electrical disasters.
- 社団法人 電気学会の論文
- 2005-12-01
著者
-
Kim Hyang-kon
Electrical Safety Research Institute A Subsidiary Of Korea Electrical Safety Corporation
-
CHOI Chung-Seog
Electrical Safety Research Institute, a subsidiary of Korea Electrical Safety Corporation
-
LEE Ki-Yeon
Electrical Safety Research Institute, a subsidiary of Korea Electrical Safety Corporation
-
GIL Hyoung-Jun
Electrical Safety Research Institute, subsidiary of Korea Electrical Safety Corporation
-
HAN Woon-Ki
Electrical Safety Research Institute, subsidiary of Korea Electrical Safety Corporation
-
Han Woon-ki
Electrical Safety Research Institute Subsidiary Of Korea Electrical Safety Corporation
-
Lee Ki-yeon
Electrical Safety Research Institute A Subsidiary Of Korea Electrical Safety Corporation
-
Gil Hyoung-jun
Electrical Safety Research Institute Subsidiary Of Korea Electrical Safety Corporation
-
Choi Chung-seog
Electrical Safety Research Institute A Subsidiary Of Korea Electrical Safety Corporation
関連論文
- Temperature diffusion distribution of electric wire deteriorated by overcurrent (特集:平成19年[電気学会]電力・エネルギー部門大会)
- Flame Spread and Damaged Properties of RCD Cases by Tracking (特集:平成18年〔電気学会〕電力・エネルギー部門大会)
- The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model (特集:平成17年〔電気学会〕電力・エネルギー部門大会)
- Analysis of Dispersive Characteristics and Structures of Copper Wire Melted by Overcurrent (特集:平成17年〔電気学会〕電力・エネルギー部門大会)